| Plan Review Notes For Permit 04080551 |
| Permit Number |
04080551 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-26 00:00:00 | DENIED: | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.ENERGY CALCULATIONS INDICATE | | | ADDITION.THE SQUARE FOOTAGE INDICATED | | | ON THE ENERGY CALCULATIONS WOULD SEEM | | | TO BE FOR THE ENTIRE HOUSE.IS THE | | | A/C SYSTEM NEW OR EXISTING? | | | | | | 2.PROVIDE PLANS INDICATING DUCT AND | | | GRILLE SIZE, MATERIAL AND LAYOUT.SHOW | | | NEW DUCTWORK ONLY.SHOW WHERE THE NEW | | | DUCT WILL TIE INTO THE EXISTING DUCTWORK | | | | | | 3.SHOULD THE ENTIRE HOUSE BE A NEW | | | A/C SYSTEM, PROVIDE PLANS FOR ALL NEW | | | DUCTWORK. | | | | | | 4.INDICATE IF THE A/C EQUIPMENT IS | | | NEW OR EXISTING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|