| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE #6 EQUIPMENT GROUND FROM THE |
| | METER TO THE PANEL MUST BE REMOVED PER |
| | 250.6 AS IT ALLOWS A PARALLEL PATH TO |
| | GROUND. |
| | |
| | 2} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT PER110.9. |
| | |
| | 3} PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 4} IF THERE IS NO DISCONNECT AT THE |
| | METER PLEASE SEE 230.70 CWPB |
| | AMMENDMENTS FOR REQUIREMENT REGARDING |
| | UNPROTECTED CONDUCTORS INSIDE THE |
| | BUILDING. |
| | |
| | 5} A SERVICE RECEPTACLE MUST BE ADDED |
| | FOR THE A/C PER 210.63. |
| | |
| | 6} PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING PER |
| | 210.52(E). |
| | |
| | 7} SMOKE DETECTORS ARE REQUIRED AT THE |
| | STAIRS PER 905.2.2 FBC. |
| | |
| | 8} THE RECEPTACLE IN THE GARAGE AT THE |
| | PANEL MUST BE GFI PER 210.8(A)(2). |
| | |
| | 9} THE KITCHEN COUNTERTOP RECEPTACLES |
| | MUST BE GFI PER 210.8(A)(6) AND SPACED |
| | PER210.52(C). |
| | |
| | 10} A RECEPTACLE MUST BE ADDED AT THE |
| | PENINSULAR PER210.52(C)(3). |
| | |
| | 11} PER 61G1-16.004 THE FIRMS BUSINESS |
| | LICENSE NUMBER(AA) MUST APPEAR IN THE |
| | TITLE BLOCK. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |