| Plan Review Notes For Permit 04080478 |
| Permit Number |
04080478 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-12-20 00:00:00 | RESPONSE TO FAX DATED 12/15/04 | | | ***NOT A PLAN REVIEW*** | | | | | | AS DISCUSSED, | | | | | | 1.)PERMIT CANNOT BE ISSUED WITHOUT | | | IMPACT FEES.PLEASE SUBMIT BOTH STAMP | | | AND RECEIPT. | | | | | | 2.)THE PERMIT CAN BE ISSUED WITH A | | | PROVISO THAT A SEPARATE PERMIT BE | | | REQUIRED FOR THE SKYLIGHTS. | | | | | | 3.)FAXED LETTER FROM THE ENGINEER WAS | | | RECEIVED.IT STATES THAT THE ROOF IS | | | ZONE 1, EFFECTIVE WIND AREA FROM 50 - | | | 100 SF.WHAT ABOUT ZONE 2&3?HOW WAS | | | THE EFFECTIVE WIND AREA OF 50-100 SF | | | FOR | | | ZONE 1 DETERMINED?PROVIDE EFFECTIVE | | | WIND AREA FOR ZONE 2 AND 3 WITH | | | PRESSURES. | | | | | | 4.)CORRECTION #4 REMOVED FROM THE | | | LIST. | | | | | | 5.)4X PLAN REVIEW FEE IS A MANDATORY | | | FEE SET BY FLORIDA STATUTE AFTER THE | | | THIRD TIME A COMMENT HAS NOT BEEN | | | ADDRESSED.THIS FEE WOULD NOT APPLY TO | | | COMMENTS 1&2.SHOULD COMMENTS 3 & 4 | | | NOT | | | BE CLEAR, PLEASE CONTACT ME BEFORE | | | RESUBMITTING. | | | |
|