| 2004-09-16 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) MORE INFORMATION REQUIRED. INDICATE |
| | THE TYPE OF BUSINESS, AND EXPLAIN WHAT |
| | DRAWING ROOMS ARE. |
| | 2) WATER COOLER SHALL BE ARI-1010 COM- |
| | PLIANT. SUBMIT MANUF. SPECIFICATIONS. |
| | SECTION 410.1 |
| | 3) SINK IN BREAKROOM SHALL COMPLY WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | SUBMIT A DETAIL. |
| | 4) ACCESSIBLE TOILET ROOM SHALL COMPLY |
| | WITH 11-4.16, 11-4.19, & 11-4.22 AND ALL |
| | SUBSECTIONS. SUBMIT A DETAIL. - W/C |
| | SHALL BE 18" FROM CENTER OF FIXTURE TO |
| | THE WALL, AND LAV SHALL BE MIN. 15" OFF |
| | WALL TO CENTER OF FIXTURE. SHOW THESE |
| | MEASUREMENTS ON THE DETAIL. SECTION |
| | 104.2.1 |
| | 5) ORIGINAL SIGNATURE IS REQUIRED ON THE |
| | SEAL OF EACH SHEET. FAC 61G1-16.004(5) |
| | AND FS 481.2055 SIGNATURE STAMPS ARE NOT |
| | APPROVED. |
| | 5) SHT 2 SANITARY RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| | CODE REQUIREMENTS. |
| | A) BREAK ROOM SINK NOT SHOWN ON RISER. |
| | C) DRY HORIZONTAL VENTS ARE NOT APPROV- |
| | ED. SECTION 905.3 |
| | D) LAVS IN ACCESSIBLE TOILET ROOM AND |
| | ADJACENT TOILET ROOM ARE NOT VENTED AND |
| | ARE "S" TRAPS WHICH ARE NOT APPROVE. |
| | SECTION 1002.3(5) |
| | E) W/C'S ON RISER DIAGRAM SHALL NOT BE |
| | TRAPPED AS THEY HAVE AN INTEGRAL TRAP IN |
| | THE FIXTURE AND THEY WILL BE DOUBLE TRA- |
| | PPED. SECTION 1002.1 |
| | (SEE RED LINE CORRECTIONS ON RISER FOR |
| | EXAMPLES OF HOW TO CORRECT RISER.) |
| | 6) SUBMIT A WATER RISER DIAGRAM. SECTION |
| | 104.3.1.1 |
| | 7) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. SECTION 608.13.2 |
| | 8) INDICATE WHAT WILL BE PROCESSED IN |
| | THE PROCESSING ROOM. IF CHEMICALS/METALS |
| | ARE USED IN THE PROCESSING A DILUTION |
| | TANK OR SEPARATOR MAY BE REQUIRED. |
| | SECTION 104.2.1 |
| | 9) SECTION 903.1 EACH SANITARY DRAINAGE |
| | SYSTEM SHALL HAVE ONE MAIN VENT STACK |
| | THAT WILL EXTEND THROUGH TO THE OPEN AIR |
| | |
| | REVIEW BY KEN STEVENS |