| 2004-08-24 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04080473 |
| | ADD: 1500 N DIXIE # 308 |
| | CONT: D. F. CONTRACTORS INC |
| | TEL: (561)502-1761 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)1012.1.4. DURING ITS SWING, ANY |
| | DOOR IN A MEANS OF EGRESS SHALL LEAVE |
| | UNOBSTRUCTED AT LEAST 1/2 OF THE REQUIRE |
| | REQUIRED WIDTH OF AN AISLE, CORRIDOR, |
| | PASSAGEWAY, OR LANDING, NOR PROJECT MORE |
| | THAN 7" INTO THE REQUIRED WIDTH. |
| | |
| | 3)11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 5)1204.2 SURROUNDING MATERIALS; |
| | THE WALLS & FLOORS OF ALL PUBLIC REST- |
| | ROOMS SHALL BE LINED WITH NONABSORBANT |
| | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| | FLOOR. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |