| Plan Review Notes For Permit 04080447 |
| Permit Number |
04080447 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-18 00:00:00 | *********** UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE PLANS CONTAIN WHITE- | | | -OUT AND HANDDRAWN CHANGES MADE TO | | | SIGNED AND SEALED DRAWINGS. | | | PLEASE HAVE ANY CHANGES RE-PRINTED AND | | | RE-SIGNED AND SEALED BY THE ENGINEER OF | | | RECORD. FS 471.025 | | | | | | 2)NOTE: PLEASE CORRELATE LOADS, AHU #1 | | | SHOWS 4200,420? PLEASE SEE OCP AND AWG | | | FOR AIR COMPRESSOR. | | | ONE SET OF PLANS HAS SOME OF THESE ITEMS | | | REDLINED. | | | | | | 3)NOTE: PLEASE SEE PLANS SHOW A NEW | | | ELECTRICAL PANEL BEING INSTALLED, HOW- | | | -EVER RISER DOES NOT INDICATE THIS? | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | WHICH MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | TWO COMPLETE SETS FOR REVIEW AND STAMP- | | | -ING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|