| Plan Review Notes For Permit 04080445 |
| Permit Number |
04080445 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-13 00:00:00 | | | | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | | EXISTING LOADS AND THE EXISTING OR | | | PROPOSED SERVICE SPECIFICATIONS PER | | | 215.15. | | | THE ELECTRICAL CONTRACTOR MUST SUBMIT | | | SAME AT TIME OF APPLICATION. THE | | | ELECTRICAL CONTRACTOR MUST SHOW THAT | | | THE SERVICE IS ADEQUITE AND HAVE THE | | | CALCULATIONS REVIEWED PRIOR TO CALLING | | | INSPECTIONS, AND POST THE CALCULATIONS | | | WITH THE PERMIT | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|