| Plan Review Notes For Permit 04080408 |
| Permit Number |
04080408 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-18 00:00:00 | ************* UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE 210.12B OF 2002 NEC | | | FOR ARC FAULT PROTECTION REQUIRED FOR | | | BEDRMS. | | | PLEASE ADJUST CIRCUITING. | | | | | | 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE | | | AND RISER. RISER MENTIONS, 1 1/2 CONDUIT | | | AND PANEL SCHEDULE MENTIONS CABLE FOR | | | FEEDERS?? | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATING FOR NEW | | | MCB BRKRS. 110.9/215.5 | | | | | | 4)NOTE: PLEASE SEE PLANS ARE MISSING | | | REQUIRED TITLE BLOCK FOR ENGINEER. | | | FAC 61G15-23.002. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|