| 2004-12-14 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | COMMENTS FROM THE PREVIOUS REVIEW, |
| | ITEMS |
| | #3 AND #4 WERE NOT ADDRESSED.PLANS |
| | ARE |
| | DATED 8/3 AND 8/6, SAME PLANS AS |
| | REVIEWED PREVIOUSLY WITH NO REVISIONS. |
| | |
| | FOR YOUR CONVENIENCE, THE PREVIOUS |
| | COMMENTS ARE AS FOLLOWS: |
| | |
| | 1.)PROVIDE DESIGN LOAD INFORMATION ON |
| | THE PLAN AS WELL AS THE INFORMATION |
| | REQUIRED BY FBC1609.1.72003 |
| | AMENDMENTS. |
| | |
| | 2.)SHOW FBC TABLE 500 COMPLIANCE; |
| | PROVIDE AREAS OF EXISTING BUILDING, |
| | ADDITION AREA, DECLARE BUILDING TYPE, |
| | SPRINKLED OR NONSPRINKLED AND |
| | OCCUPANCY. |
| | |
| | 3.)SHOW HOW THE PANELS MEET FIRE |
| | RESISTANCE REQUIREMENTS.CANOPIES IN |
| | THE FIRE DISTRICT ARE TO CONFORM WITH |
| | THE CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC, SECTION F102.2.8.ROOF |
| | PANELS ARE NOT REQUIRED TO HAVE FIRE |
| | RESISTANCE RATING UNLESS FIRE |
| | RESISTANCE |
| | RATING IS REQUIRED FBC1604.5(2).ROOF |
| | FIRE RESISTANCE RATING IS REQUIRED CITY |
| | OF WEST PALM BEACH AMENDMENTS TO THE |
| | FBC |
| | F102.2.4. |
| | |
| | 4.)SHOW HOW QUALITY ASSURANCE WILL BE |
| | ADDRESSED (LOCAL PRODUCT APPROVAL |
| | APPLICATION), FAC9B-72. |
| | |
| | 5.)SEE ATTACHED FS553.80(2)(B). |
| | |
| | |