| 2004-08-31 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)THE PLANS SHOW A "FUTURE GARAGE". |
| | PLEASE NOTE THAT COMPLIANCE WITH THE |
| | BUILDING CODE OR CODES WHICH WILL BE IN |
| | EFFECT AT THE TIME OF SUBMITTAL HAS NOT |
| | PERFORMED FOR THIS FUTURE STRUCTURE |
| | RELATIVE TO THIS AWNING. |
| | |
| | 2.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED FOR THE ROOF,FAC9B-72. |
| | SEE WWW.FLORIDABUILDING.ORG.AN |
| | APPLICATION WAS SUBMITTED BUT IS |
| | INCOMPLETE.PLEASE NOTE THAT ITEM |
| | #2, 7 THROUGH 10 ARE INCOMPLETE.PLEASE |
| | SEE ATTACHED APPLICATION WITH CHECKLIST. |
| | ORIGINAL DOCUMENTS REQUIRED, INCLUDING |
| | SEALED TEST REPORT.A COPY OF A TEST |
| | REPORT WHICH I FOUND ON THE INTERNET |
| | IS INCLUDED FOR YOUR CONVENIENCE.IT |
| | IS THE RESPONSIBILITY OF THE DESIGNER |
| | TO DETERMINE WHETHER OR NOT THIS IS |
| | THE PRODUCT YOU WISH TO INSTALL. |
| | ALSO PLEASE SEE THE VALIDATION CHECKLIST |
| | TO ASSIST YOU IN FILLING OUT THIS FORM. |
| | ADDITIONAL INFORMATION IS ALSO |
| | AVAILABLE IN THE RULE 9B-72 FOUND AT |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | 3.)PROVIDE DESIGN LOAD INFORMATION |
| | ON THE PLAN AS WELL AS THE INFORMATION |
| | (WIND LOAD) REQUIRED BY FBC1609.1.7, |
| | 2003 AMENDMENTS. |
| | |
| | 4.)YOU ARE CONNECTING TWO EXISTING |
| | BUILDINGS TO BECOME ONE STRUCTURE. |
| | PROVIDE AREAS OF THE EXISTING BUILDINGS, |
| | DECLARE BUILDING TYPE AND OCCUPANCY, |
| | SHOW COMPLIANCE WITH FBC TABLE 500. |
| | |
| | 5.)THE TEST REPORT WHICH I OBTAINED |
| | FROM THE INTERNET (ENCLOSED) INDICATES A |
| | FAILURE OF THE PANELS AT 161.2.THE |
| | DECK CONNECTION ANALYSIS SHOW A DESIGN |
| | PRESSURE OF -128.2 FOR ZONE 3.WHERE |
| | IS THE SAFETY FACTOR FOR THE PANELS, |
| | WHICH DO NOT APPEAR TO BE COMPLIANT |
| | FOR ZONE 3 (ALTHOUGH THE CONNECTORS |
| | ARE APPARENTLY COMPLIANT)?IS THIS |
| | TEST FOR THE SAME PRODUCT? |
| | |
| | 6.)DELEGATED ENGINEERING IS TO BE |
| | REVIEWED BY THE DESIGNER OF RECORD, |
| | PLEASE REVIEW FAC61G15-30.005, .006. |
| | DESIGN PERFORMED BY DELEGATED ENGINEER |
| | IS TO BE IN CONFORMANCE WITH THE PLAN, |
| | WHICH IS LACKING DESIGN CRITERIA. |
| | |
| | 7.)FOR THE CONNECTOR CALCS, A TITLE |
| | BLOCK WITH ALL INFORMATION REQUIRED |
| | BY FAC61G15-23.002 IS REQUIRED. |