| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT PER 110.9. |
| | |
| | 2} THE ELECTRODE MUST BE CONNECTED TO |
| | FOOTER STEEL PER 250.52(A)(3). |
| | |
| | 3} THE SMOKE DETECTORS MUST BE ON AN |
| | ARC FAULT CIRCUIT PER 210.12, THE NOTES |
| | REGARDING THE KITCHEN OR BATHROOM |
| | CIRCUIT WOULD INDICATE THEY WOULD NOT |
| | BE ARC FAULT PROTECTED. PLEASE CLARIFY. |
| | |
| | 4} PLEASE PROVIDE A PANEL SCHEDULE SO |
| | BRANCH CIRCUIT COMPLIANCE CAN BE |
| | DETERMINED.210.12, 210.11(C) ALL,ETC. |
| | |
| | 5} IT IS UNCLEAR WHETHER THE MAIN PANEL |
| | IS LOCATED NEXT TO THE METER OR |
| | ELSEWHERE. PLEASE CLARIFY AND BE AWARE |
| | OF ARTICLE 230.70 WPB AMMENDMENTS |
| | REGARDING SERVICE DISCONNECTING MEANS. |
| | |
| | 6} PLEASE SEE THAT RECEPTACLE SPACING |
| | DOES NOT COMPLY WITH 210.52(A)(1) & (2) |
| | IN THE LIVING ROOM, MASTER BEDROOM AND |
| | BEDROOM #2, SEE REVIEWED SET OF PLANS. |
| | |
| | 7} THE MASTER BATH NEEDS A RECEPTACLE |
| | (GFI) TO COMPLY WITH 210.52(D). |
| | |
| | 8} PLEASE SEE MISSING RECEPTACLE IN THE |
| | FRONT PER 210.52(E). |
| | |
| | 9} THE ISLAND RECEPTACLE (KITCHEN) MUST |
| | BE GFI PER 210.8(A)(6). |
| | |
| | 10} THE BATH OFF THE DINING ROOM MUST |
| | HAVE A GFI PER 210.52(D). |
| | |
| | 11} PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |