| 2004-09-21 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) SUBMIT (2) COPIES OF LOT SURVEY. |
| | |
| | 3) SUBMIT AN ADDITIONAL COPY OF THE SOIL |
| | REPORT. |
| | |
| | 4) SPECIFY THE METHOD OF TERMITE |
| | PROTECTION THAT WILL BE USED ON THE |
| | PLANS. SEE FBC 1816. |
| | |
| | 5) CITY OF WEST PALM BEACH AMENDMENTS TO |
| | FBC TABLE 2306.1 REQUIRES ROOF SHEATHING |
| | TO BE NAILED WITH 8D RING SHANK NAILS IN |
| | ZONE 3 FOR STRUCTURES WITH A MEAN ROOF |
| | HEIGHT OF 25'-35'. REVISE SHEET S3. |
| | |
| | 6) SPECIFY ON THE PLANS THAT DOWNSPOUTS |
| | ARE REQUIRED TO DISCHARGE AT LEAST ONE |
| | FOOT FROM EXTERIOR WALLS AS REQUIRED BY |
| | FBC 1804.1.6 AND 1503.4.4. |
| | |
| | 7)2304.3.4 WOOD JOIST SHALL HAVE 18" |
| | CLEARENCE FROM THE BOTTOM OF JOIST TO |
| | EARTH OR ELSE BE PRESSURE TREATED WOOD |
| | OR NATURALLY PRESERVATIVE WOOD. |
| | |
| | 8) SUBMIT (2) COPIES OF THE ENERGY CALCS |
| | AND MANUAL "J"S AS REQUIRED BY FBC |
| | CHAPTER 13. NOTE: OWNER/AGENT IS |
| | REQUIRED TO SIGN THE FORM. |
| | |
| | 9) SUBMIT SHOP DRAWINGS OF EXTERIOR |
| | GUARDRAILS FOR APPROVAL BEFORE THEY ARE |
| | INSTALLED. |
| | |
| | 10) PROVIDE DETAILS OF FIREPLACE AND |
| | CHIMNEY CONSTRUCTION. SHOW COMPLIANCE |
| | WITH FBC SECTIONS 2113 AND 2114. FBC |
| | 2804.2.4 REQUIRES THE CHIMNEY TO EXTEND |
| | 3' ABOVE THE HIGHEST POINT WHERE IT |
| | PASSES THROUGH THE ROOF AND AT LEAST 2' |
| | HIGHER THAN ANY PORTION OF THE ROOF OR |
| | BUILDING WITHIN 10' HORIZONTALLY. |
| | |
| | 11) SUBMIT PRODUCT APPROVAL AND |
| | MANUFACTURER'S SPECIFICATIONS FOR THE |
| | FLAT DECK ROOF INSULATION. |
| | |
| | 12)THE ROOFING MATERIAL/SYSTEM MANUFACT- |
| | URE SHALL PROVIDE AN AFFIDAVIT CERTIFY- |
| | ING THE USE OF THEIR PRODUCT OVER AN |
| | UNVENTED ATTIC SYSTEM. SEE ATTACHMENT. |
| | |
| | 13) SPECIFY FIREBLOCKING IN CONCEALED |
| | SPACES BETWEEN STAIR STRINGERS AT THE |
| | TOPS AND BOTTOMS OF RUNS ON S2. SEE |
| | FBC 2305.1.4(3). |
| | |
| | 14)CHANGE REFERENCE TO STANDARD BUILDING |
| | CODE TO FLORIDA BUILDING CODE IN NOTE D |
| | UNDER WOOD FRAMING ON S3. |
| | |
| | 15) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 16) SUBMIT STATE/LOCAL PRODUCT APPROVALS |
| | FOR THE FOLLOWING: |
| | - STRUCTURAL MULLIONS |
| | - ARCHED TOP FIXED GLASS WINDOWS |
| | - ROUND FIXED GLASS WINDOWS |
| | - FIXED GLASS WINDOWS ABOVE FRENCH DOORS |
| | |
| | 17) SOME OF THE NOAS SUBMITTED HAVE |
| | DRAWINGS THAT ARE MISSING INFORMATION |
| | DUE TO DOWNLOADING WITHOUT SHRINKING THE |
| | PAGES TO FIT ON 8-1/2" X 11" PAPER. TWO |
| | COPIES OF EACH PRODUCT APPROVAL IS |
| | REQUIRED. |
| | |