| Plan Review Notes For Permit 04080359 |
| Permit Number |
04080359 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-16 00:00:00 | ************* UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE FAC 61G15-23.002 | | | PLEASE SEE THE PRINTED NAME AND LICENSE | | | # OF ENGINEER OS ALSO REQUIRED ON TITLE | | | BLOCK. | | | | | | 2)NOTE: PLEASE INLCLUDE ALL CIRCUITING | | | ON PLANS AND CORRELATE WITH A PANEL | | | SCHEDULE TO BE SUBMITTED SHOWING ALL | | | MIN REQUIRED CIRCUITS UNDER 2002 NEC. | | | 210.52,210.11C1,C3. | | | | | | 3) NOTE: PLEASE LIST ALL THE REQ'D | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.52D, 210.11C3 | | | | | | 4) NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210.8A-6 | | | | | | 5)NOTE: PLEASE SEE THAT HANDWRITTEN | | | CHANGES TO PLANS MAY NOT BE DONE TO PLAN | | | 'S WHICH ARE SIGNED AND SEALED BY THE | | | ENGINEER. | | | FS 471.025 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|