2004-08-16 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002
 PLEASE SEE THE PRINTED NAME AND LICENSE
 # OF ENGINEER OS ALSO REQUIRED ON TITLE
 BLOCK.
  
 2)NOTE: PLEASE INLCLUDE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED SHOWING ALL
 MIN REQUIRED CIRCUITS UNDER 2002 NEC.
 210.52,210.11C1,C3.
  
 3) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 4) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 5)NOTE: PLEASE SEE THAT HANDWRITTEN
 CHANGES TO PLANS MAY NOT BE DONE TO PLAN
 'S WHICH ARE SIGNED AND SEALED BY THE
 ENGINEER.
 FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  