| 2004-08-26 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT:04080335 |
| | ADD: 643 33RD STREET |
| | CONT:NORTHWOOD BUSINESS DEV CORP |
| | TEL: (561)832-7959 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | PLEASE INDICATE CLEARLY WHERE EACH |
| | COMPONENT FOR TIE WILL BE USED. |
| | |
| | 2) INFO. GUARDRAILS SHALL HAVE |
| | INTERMEDIATE RAILS OR ORNAMENTAL |
| | PATTERN SUCH THAT A 4" DIAMETER SPHERE |
| | CANNOT PASS THROUGH ANY OPENING UP TO A |
| | HEIGHT OF 34". A BOTTOM RAIL OR CURB |
| | SHALL BE PROVIDED THAT WILL REJECT THE |
| | PASSAGE OF 2" DIAMETER SPHERE. ALSO |
| | PLEASE FBC. SEC.1015 AND SEC.1608.2.3 |
| | |
| | 3)1507.3.8. ASPHALT SHINGLES LOW |
| | SLOPE ROOFING, UNDERLAYMENT APPLICATION |
| | FOR ROOF SLOPES FROM 2:12 UP TO 4:12, |
| | UNDERLAYMENT SHAL BE A MINIMUM OF TWO |
| | LAYERS APPLIED AS FOLLOWS: |
| | 1) STARTING AT THE EAVE, A 19-INCH |
| | STRIP OF UNDERLAYMENT SHALL BE APPLIED |
| | PARALLEL WITH THE EAVE AND FASTENED |
| | SUFFICIENTLY TO STAY IN PLACE. |
| | 2) STARTING AT THE EAVE, 36-INCH-WIDE |
| | STRIPS OF UNDERLAYMENT FELT SHALL BE |
| | APPLIED OVER LAPPING SUCCESSIVE SHEETS |
| | 19 INCHES AND FASTENED SUFFICIENTLY TO |
| | STAY IN PLACE. (PLEASE SHOW ROOF SLOPE) |
| | |
| | 4) IS THE STRUCTURE OF THE HOUSE MADE |
| | OF WOOD OR CONCRETE BLOCK? PLEASE |
| | PROVIDE THIS INFORMATION SO WE CAN BE |
| | SURE THE BEAMS ARE ATTATCH TO CODE. |
| | |
| | 5) PLEASE INDICATE THE SPACING OF THE |
| | 3/8" BOLTS ON THE DRAWINGS. |
| | |
| | 6) WPB AMENDEMENTS SEC.104.2.1 |
| | DRAWINGS AND INFORMATION SHALL BE |
| | SPECIFIC. ALL INFORMATION,DRAWINGS, |
| | SPECIFICATIONSAND ACCOMPANYING DATA SHAL |
| | L BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. ALSO |
| | SEE SEC.104.2.1.3 |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6726 |
| | FAX: (561)659-8026 |