Plan Review Notes
Plan Review Notes For Permit 04080325
Permit Number 04080325
Review Stop E
Sequence Number 6
Notes
Date Text
2005-08-04 00:00:00******** UNSAT ********
  
 1)NOTE: PLEASE SEE PREVIOUS PLANS WERE
 NOTED ABOUT CONTINUOUS LOADS, PLEASE SEE
 CONTINUOUS LOADS (PUMP/VAL PAK AND HEAT
 PUMP) ON POOL SUB PANEL ARE TO BE SHOWN
 AT 125% ON SUB PANEL. THIS LOAD WOULD
 JUST BE CARRIED OVER TO THE LOAD ON MAIN
 PANEL. IT IT SHOWN AT 125% ON MAIN
 PANEL, JUST NOT SUB PANEL.
 215.3,680.9,230.42 ETC
  
 2)NOTE: PLEASE SEE A SINK? APPEARS TO BE
 SHOWN DIRECTLY INFRON OF PANEL "A"?
 110.26
  
 3)NOTE: PLEASE SEE PLANS ARE NOT SEALED
 BY ARCHITECT OF RECORD.
 PLEASE SEE FS 481.221
  
 PLEASE ADDRESS NOTES ONE AND TWO SINCE
 PLANS ARE COMING BACK FOR NOTE #3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  