| Plan Review Notes For Permit 04080325 |
| Permit Number |
04080325 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2005-08-04 00:00:00 | ******** UNSAT ******** | | | | | | 1)NOTE: PLEASE SEE PREVIOUS PLANS WERE | | | NOTED ABOUT CONTINUOUS LOADS, PLEASE SEE | | | CONTINUOUS LOADS (PUMP/VAL PAK AND HEAT | | | PUMP) ON POOL SUB PANEL ARE TO BE SHOWN | | | AT 125% ON SUB PANEL. THIS LOAD WOULD | | | JUST BE CARRIED OVER TO THE LOAD ON MAIN | | | PANEL. IT IT SHOWN AT 125% ON MAIN | | | PANEL, JUST NOT SUB PANEL. | | | 215.3,680.9,230.42 ETC | | | | | | 2)NOTE: PLEASE SEE A SINK? APPEARS TO BE | | | SHOWN DIRECTLY INFRON OF PANEL "A"? | | | 110.26 | | | | | | 3)NOTE: PLEASE SEE PLANS ARE NOT SEALED | | | BY ARCHITECT OF RECORD. | | | PLEASE SEE FS 481.221 | | | | | | PLEASE ADDRESS NOTES ONE AND TWO SINCE | | | PLANS ARE COMING BACK FOR NOTE #3. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|