| 2005-07-08 00:00:00 | ********* UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE 250.66 ,310.16 FOR | | | SIZING OF MIN GROUNDING ELECTRODE | | | CONDUCTOR. #2 MIN. | | | PREVIOUS REVIEW. | | | | | | 2)NOTE:PLEASE SEE ALL CONTINUOUS LOADS | | | ARE TO BE SHOWN AT 125%. | | | PLEASE SEE ONLY CONTINUOUS ARE TO BE | | | INDICATED AS "CONTINUOUS LOADS". | | | PLEASE SEE ART 100 NEC FOR DEFINITION OF | | | CONT LOADS. | | | CONTINUOUS LOAD. A LOAD WHERE THE | | | MAXIMUM CURRENT IS EXPECTED TO CONTINUE | | | FOR 3 HOURS OR MORE. | | | | | | PLEASE SEE SERVICE ETC IS BEING SHOWN AS | | | ALL BEING CONT??? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|