Plan Review Notes
Plan Review Notes For Permit 04080325
Permit Number 04080325
Review Stop E
Sequence Number 4
Notes
Date Text
2005-07-08 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE 250.66 ,310.16 FOR
 SIZING OF MIN GROUNDING ELECTRODE
 CONDUCTOR. #2 MIN.
 PREVIOUS REVIEW.
  
 2)NOTE:PLEASE SEE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%.
 PLEASE SEE ONLY CONTINUOUS ARE TO BE
 INDICATED AS "CONTINUOUS LOADS".
 PLEASE SEE ART 100 NEC FOR DEFINITION OF
 CONT LOADS.
 CONTINUOUS LOAD. A LOAD WHERE THE
 MAXIMUM CURRENT IS EXPECTED TO CONTINUE
 FOR 3 HOURS OR MORE.
  
 PLEASE SEE SERVICE ETC IS BEING SHOWN AS
 ALL BEING CONT???
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717