| Notes |
| Date |
Text |
| 2005-01-03 00:00:00 | ******** PROVISO/REVISION *********** | | | | | | PLEASE SEE SOME NOTES FROM PREVIOUS | | | REVIEWS. | | | | | | 1)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS FROM MAINS TO | | | PANELS. | | | EQUIPMENT GRNDS REQUIRED AFTER THE FIRST | | | MEANS OF DISC. 250.24, 250.110, SIZE PER | | | 250.122 | | | | | | 2)NOTE: PLEASE SEE MIN GROUNDING | | | ELECTRODE CONDUCTOR PER 250.66 1/0. | | | | | | 3)NOTE: PLEASE SEE CIRCUITING FOR EM | | | LTS | | | PER 700.12E WITH LOCAL LIGHTING BRANCH | | | CIRCUIT. | | | | | | PLEASE REVISE THE ABOVE ALONG WITH ANY | | | OTHER REVISIONS BEFORE ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. | | | IF THERE ARE ANY QUESTIONS, PLEASE | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|