| Date |
Text |
| 2004-11-18 00:00:00 | ***** UNSAT 2ND REVIEW ***** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: NOTE #1 OK |
| | |
| | 2)NOTE: NOTE #2 OK |
| | |
| | 3)NOTE: NOTE #3 OK |
| | |
| | 4)NOTE: NOTE #4 OK |
| | |
| | 5)NOTE: NOTE #5 NO. |
| | PLEASE SEE 250.24, 250.110 FOR EQUIPMENT |
| | GROUNDING AFTER THE FRIST MEANS OF |
| | DISCONNECT. SIZED PER 250.122 |
| | |
| | 6)NOTE: NOTE #6 NO. |
| | PLEASE SHOW LOAD CALCULATIONS, PLEASE |
| | SHOW PER 220.3,220.10,220.11,220.13 |
| | ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 7)NOTE: NOTE #7 NO. |
| | PLEASE SEE EM/EXT LTS ARE NOW SHOWN ON A |
| | SEPARATE CIRCUIT. PLEASE SEE 700.12E FOR |
| | CIRCUITING TO LOCAL AREA LIGHTING. |
| | |
| | *NEW NOTE DUE TO CHANGES IN PLANS. |
| | |
| | 1)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | DETAIL HAS NOW ADDED PARALLEL #6'S FOR |
| | GROUNDING ELECTRODE CONDUCTOR. |
| | |
| | |
| | 2)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONAL. |
| | THIS IS ONLY GIVEN AS A NOTICE AT THIS |
| | TIME. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWS WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | |
| | |
| | THIS IS NOT PERMITTED, MAY ONLY USE THE |
| | #2 AS ALSO SHOWN. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |