Plan Review Notes
Plan Review Notes For Permit 04080325
Permit Number 04080325
Review Stop P
Sequence Number 1
Notes
Date Text
2004-09-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 PER TABLE 403.1 A SERVICE
 SINK IS REQUIRED.
 2) SUBMIT A DETAIL FOR THE URINAL TO
 SHOW COMPLIANCE WITH SECTION 11-4.18 AND
 ALL SUBSECTIONS.
 3) A WATER RISER DIAGRAM IS REQUIRED PER
 SECTION 104.3.1.1
 4) SHT A-5 THE SANT. RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN.
 A) THE W/C'S AND LAVS IN THE HANDCAP
 STALLS ARE REVERSED. SHOULD HAVE THE LAV
 ON THE LEFT SIDE OF THE W/C. SECTION
 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved