| Plan Review Notes For Permit 04080325 |
| Permit Number |
04080325 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-09-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-2 PER TABLE 403.1 A SERVICE | | | SINK IS REQUIRED. | | | 2) SUBMIT A DETAIL FOR THE URINAL TO | | | SHOW COMPLIANCE WITH SECTION 11-4.18 AND | | | ALL SUBSECTIONS. | | | 3) A WATER RISER DIAGRAM IS REQUIRED PER | | | SECTION 104.3.1.1 | | | 4) SHT A-5 THE SANT. RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN. | | | A) THE W/C'S AND LAVS IN THE HANDCAP | | | STALLS ARE REVERSED. SHOULD HAVE THE LAV | | | ON THE LEFT SIDE OF THE W/C. SECTION | | | 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|