2004-08-18 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE CORRELATE ELECTRICAL
 PLANS W/ MECHANICAL PLANS.
 MECH PLANS SHOW TWO A/C SYSTEMS.
 PLEASE ALSO SEE OCP FOR A/C SYSTEMS
 ALONG WITH LOAD CALCULATIONS.
  
 3)NOTE: PLEASE CORRELATE RISER WITH
 PLANS. PLANS SHOW TWO NEW PANELS? A&B
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 MAIN.
  
 5 )NOTE: PLEASE SHOW /CLARIFY METHOD
 OF THE EQUIPMENT GROUNDING BETWEEN
 MAIN MEANS OF DISC AND PANELS/GUTTERS.
 250.110,250.24
 PLEASE SIZE ALL EQUIPMENT GROUNDING
 CONDUCTORS PER 250.122
  
 6)NOTE: PLEASE SEE THIS IS CONSIDERED
 A COMMERCIAL BLDG.
 PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 NEEDS TO REFLECT.
  
 7)NOTE: PLEASE SEE 700.12E FOR CIRCUIT--
 -ING OF EM/EXT LTS.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  