| 2004-08-18 00:00:00 | ************* UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | |
| | 2)NOTE: PLEASE CORRELATE ELECTRICAL |
| | PLANS W/ MECHANICAL PLANS. |
| | MECH PLANS SHOW TWO A/C SYSTEMS. |
| | PLEASE ALSO SEE OCP FOR A/C SYSTEMS |
| | ALONG WITH LOAD CALCULATIONS. |
| | |
| | 3)NOTE: PLEASE CORRELATE RISER WITH |
| | PLANS. PLANS SHOW TWO NEW PANELS? A&B |
| | |
| | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | MAIN. |
| | |
| | 5 )NOTE: PLEASE SHOW /CLARIFY METHOD |
| | OF THE EQUIPMENT GROUNDING BETWEEN |
| | MAIN MEANS OF DISC AND PANELS/GUTTERS. |
| | 250.110,250.24 |
| | PLEASE SIZE ALL EQUIPMENT GROUNDING |
| | CONDUCTORS PER 250.122 |
| | |
| | 6)NOTE: PLEASE SEE THIS IS CONSIDERED |
| | A COMMERCIAL BLDG. |
| | PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | NEEDS TO REFLECT. |
| | |
| | 7)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-- |
| | -ING OF EM/EXT LTS. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |