2004-08-16 00:00:00DENIED:
 RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.PER THE
 REVISED 2001 FBC(M) 601.4, RETURN
 TRANSFER DUCTS SHALL BE 1 1/2 TIMES THE
 SUPPLY AIR TO THAT AREA.ALL AIR INTO
 THE MASTER SUITE SHALL BE INCLUDED.
 SEE THE ATTACHED SCHEDULE FOR PROPER
 SIZING.
  