| 2005-02-22 00:00:00 | DENIED |
| | REFERENCE: FBC-424.2 SWIMMING POOLS |
| | FBC-2001 CHAPTER 1 |
| | |
| | |
| | 1) THE FOLLOWING INFORMATION IS REQUIRED |
| | ON THE PLANS EITHER IN THE FORM OF |
| | NOTES, DRAWINGS, OR SUBMITTALS: |
| | 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK. - NO |
| | VACUUM LINE IS SHOWN ON THE POOL LAYOUT |
| | SHEET, BUT A VACUUM LINE IS INDICATED ON |
| | THE PIPING SCHEMATIC. PLEASE CLAIRFY AND |
| | CORRELATE PIPING SCHEMATIC WITH POOL |
| | LAYOUT. (GIVE DETAIL, SUBMITTAL OR ADD |
| | TO NOTES) SECTION 104.2.1. |
| | 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO |
| | SUCTION INLETS SHALL BE PROVIDED FOR EA |
| | PUMP. SEPARATED BY A MINIMUM OF 3 FEET |
| | OR LOCATED ON TWO DIFFERENT PLANES. |
| | (DETAIL)- UNABLE TO READ MINIMUM |
| | SEPARATION BETWEEN MAIN DRAINS ON THE |
| | PLANS. PLEASE INDICATE 3 FT. SECTION |
| | 104.2.1. |
| | 4) SHEET WITH PIPING SCHEMATIC HAS A |
| | NOTE THAT STATES "HEATER IS EXCEMPT FROM |
| | STATE ENERGY CODE AS HEAT SOURCE IS AND, |
| | IS 90% EFICIENT". THIS IS NOT THE CASE |
| | WITH GAS POOL HEATERS AND SHALL BE |
| | DELETED FROM THE PLANS. |
| | 5) FBC-2001 424.2.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. MANUFACTURE |
| | SHEETS REQUIRED. (SUBMITTAL) |
| | 6) FBC-2001 424.2.14.2 WATER RETENTION, |
| | PROVIDE A POSITIVE MEANS OF RETAINING |
| | WATER IN THE HEATER WHEN PUMP IS SHUT |
| | OFF. (MANUF. CUT SHEETS - SUBMITTAL) |
| | 7) FBC-2001 424.2.15 GAS PIPING SHALL |
| | COMPLY WITH FBC FUEL GAS. SEPARATE PLANS |
| | AND PERMIT REQUIRED. (ADD TO NOTES) |
| | |