| 2004-11-02 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 424.2 SWIMMING |
| | POOLS |
| | FBC-2001 CHAPTER 1 |
| | |
| | FROM PREVIOUS REVIEW: |
| | 4) FBC-2001 424.2.14.1 SWIMMING POOL |
| | HEATERS SHALL BEAR THE LABEL OF A REC- |
| | OGNIZED TESTING AGENCY. MANUF. SHEETS |
| | REQUIRED. (SUBMITTAL) |
| | 5) FBC-2001 424.2.14.2 WATER RETENTION, |
| | PROVIDE A POSITIVE MEANS OF RETAINING |
| | WATER IN THE HEATER WHEN PUMP IS SHUT |
| | OFF. MANUF CUT SHEETS (SUBMITTAL) |
| | 6) FBC-2001 424.2.15 GAS PIPING SHALL |
| | COMPLY WITH FBC FUEL GAS. SEPARATE |
| | PLANS AND PERMIT REQUIRED. |
| | 8) POOL PIPING LAYOUT SHOWS MAIN DRAIN |
| | LINE CONNECTING TO ONE MAIN DRAIN, |
| | WHERE |
| | AS PIPING SCHEMATIC INDICATES |
| | CONNECTION |
| | AT THE CENTER OF THE MAIN DRAINS. (ALSO |
| | SEE APPROVED SWIMMING POOL & SPA DUAL |
| | MAIN DRAIN ATMOSPHERIC VENT ARRANGEMENT |
| | DETAIL). PER SECTION 424.2.6.6.4 THESE |
| | SUCTION INLETS SHALL BE PLUMBED SUCH |
| | THAT WATER IS DRAWN THROUGH THEM SIM- |
| | ULTANEOUSLY. CORRECT THE PIPING LAYOUT |
| | TO REFLECT THE EQUIPMENT SCHEMATIC AND |
| | DRAIN/VENT ARRANGEMENT COMPLIANT WITH |
| | SECTION 424.2.6.6. |
| | A) PLEASE ADJUST YOUR NOTES, DETAILS, |
| | OR SUBMITTALS TO REFLECT THE ABOVE |
| | INFORMATION REQUIRED FOR PLAN REVIEW. |
| | ***NEW COMMENT |
| | 1B) POOL PIPING SCHEMATIC HAS HAND |
| | DRAWN CHANGES. THIS IS NOT APPROVED. |
| | SUBMIT NEW PIPING SCHEMATIC WITH ALL |
| | APPROVED CHANGES. |
| | 2B) REMOVE ALL VOIDED SHEETS, SUBMIT |
| | 2 SETS OF PLANS FOR REVIEW AND ONE SET |
| | OF VOIDED SHEETS FOR COMPAIRSON. |
| | |
| | |