| Plan Review Notes For Permit 04080160 |
| Permit Number |
04080160 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-06-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1. SUBMIT CALCULATIONS FOR PRIMARY AND | | | SECONDARY ROOF DRAINS. SHOW TOTAL SQUARE | | | FOOTAGE OF ROOF. SHOW 1/2 AREA OF ALL | | | VERTICAL WALLS INCLUDING PARAPETS ADDED | | | TO SQUARE FOOTAGE OF ROOF IN | | | CALCULATIONS. INDICATE TOTAL SQUARE | | | FOOTAGE BEING DRAINED BY EACH ROOF | | | DRAIN. PER SECTIONS 1106 & 1107 AND ALL | | | SUBSECTIONS. | | | 2. SUBMIT A STORM RISER DIAGRAM SHOWING | | | ALL PIPE SIZES, SLOPE OF PIPE & SQUARE | | | FOOTAGE DRAINED ON PIPE. SECTION | | | 104.3.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|