2005-06-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW TOTAL SQUARE
 FOOTAGE OF ROOF. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED
 TO SQUARE FOOTAGE OF ROOF IN
 CALCULATIONS. INDICATE TOTAL SQUARE
 FOOTAGE BEING DRAINED BY EACH ROOF
 DRAIN. PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS.
 2. SUBMIT A STORM RISER DIAGRAM SHOWING
 ALL PIPE SIZES, SLOPE OF PIPE & SQUARE
 FOOTAGE DRAINED ON PIPE. SECTION
 104.3.1.
  