| Plan Review Notes For Permit 04080160 |
| Permit Number |
04080160 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-11-03 00:00:00 | ****** NOTE ****** | | | | | | ELECTRICAL PLANS ARE ON HOLD AT THIS | | | TIME ANDSHALL REMAIN IN FAILED STATUS | | | UNTIL POSSIBLE ISSUE WITH LOCATION OF | | | EXISITING GENERATOR AND GENERATOR | | | EXHAUST. | | | GENERATOR LOCATION MAY NEED TO BE MOVED | | | TO "OUTSIDE" THE BLDG. | | | EVEN WITH GENERATOR BEING EXISTING, THE | | | CONDITION IS BEING CREATED BY NEW | | | ADDITION AND SHALL ALSO MEET ANY | | | REQUIREMENTS FOR CURRENT CODES DUE TO | | | ADDITION %'S ETC WHICH FALL UNDER | | | REQUIREMENTS OF CHAPTER 34 FBC. | | | ARCHITECTUAL SHEETS DO NOT CORRELATE | | | WITH ELECTRICAL FOR LAYOUT OF WALK, COND | | | UNITS, GENERATOR ETC. | | | | | | THE LOCATION IS NOW BEING PARTIALLY | | | ENCLOSED AND ALSO CONTAINS A REQUIRED | | | EGRESS PATH. | | | FURTHER CONSULTATION WITH FIRE, | | | MEACHANICAL AND BLDG REVIEW WILL BE | | | NEEDED. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|