Plan Review Notes
Plan Review Notes For Permit 04080160
Permit Number 04080160
Review Stop B
Sequence Number 2
Notes
Date Text
2004-11-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE THE PREVIOUS LIST, ITEM #14.
 PROVIDE TWO ORIGINAL SOILS
 INVESTIGATION
 REPORTS.SIGNED, SEALED ORIGINALS
 REQUIRED FAC61G15-23.002.
  
 2.)SEE ATTACHED MISSILE IMPACT
 PROTECTION STANDARD, ITEM #14.
 REMOVABLE HURRICANE SHUTTERS ARE NOT
 ALLOWED.AS PER CONVERSATION WITH JOE
 COLOME, THE ALTERNATE #2 (SHEET A4) OF
 A SOLID WALL WILL BE USED IN LIEU OF
 WINDOWS.THIS HAS BEEN REDLINED ON THE
 PLAN; REVISION TO BE SUBMITTED BEFORE
 CONCRETE POUR.REVISE SHEETS A2, A4,
 A6, A7.
  
 3.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED FS714 (OVER 90 DAYS WITHOUT
 COMMENCING WORK).PLEASE NOTE THAT THE
 SAME CERTIFIED DOCUMENT CAN BE REFILED
 WITH THE CLERK OF COURTS FOR A NEW
 FILING DATE.
  
 4.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  