2004-08-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A1 FUTURE TENANT SPACE MINIMUM
 FIXTURE REQUIREMENTS 1 WATER CLOSET, 1
 LAV AND 1 DRINKING FOUNTAIN. TAB. 403.1
 2) SHT A2 A DRINKING FOUNTAIN IS REQUIR-
 ED FOR EXIXTING SPACE. TABLE 403.1
 3) SHT A3 CHAPTER 11 ANALYSIS & OVERFLOW
 DETAIL #6 INDICATE 5" DOWNSPOUTS, BUT
 ROOF PLAN INDICATES 4 6"X6" DOWNSPOUTS.
 PLEASE CLARIFY. SECTION 104.2.1
  