| Plan Review Notes For Permit 04080160 |
| Permit Number |
04080160 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A1 FUTURE TENANT SPACE MINIMUM | | | FIXTURE REQUIREMENTS 1 WATER CLOSET, 1 | | | LAV AND 1 DRINKING FOUNTAIN. TAB. 403.1 | | | 2) SHT A2 A DRINKING FOUNTAIN IS REQUIR- | | | ED FOR EXIXTING SPACE. TABLE 403.1 | | | 3) SHT A3 CHAPTER 11 ANALYSIS & OVERFLOW | | | DETAIL #6 INDICATE 5" DOWNSPOUTS, BUT | | | ROOF PLAN INDICATES 4 6"X6" DOWNSPOUTS. | | | PLEASE CLARIFY. SECTION 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|