| 2004-08-19 00:00:00 | *********** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SEE PLANS AND APPLICATION |
| | CALL FOR A NEW TWO-STORY BLDG, HOWEVER |
| | ONLY ELECTRICAL PLANS FOR SECOND FLR |
| | LIGHTING AND POWER WERE SUBMITTED? |
| | PLEASE SEE A MIN LTS ETC FOR LS 101 |
| | MAY BE REQUIRED. |
| | |
| | 2)NOTE: PLEASE CLARIFY GENERATOR FEED? |
| | ATS? ETC. |
| | PLEASE ALSO PROVIDE NOTE FOR SIGNAGE |
| | PER 230.2E |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 4)NOTE: PLEASE PROVIDE ALL WIND LOAD |
| | INFORMATION ON EXISTING POLES TO BE |
| | RELOCATED OR NEW POLES. |
| | FBC 140 MPH |
| | |
| | **PLEASE SEE PLANS ARE NOT COMPLETE AT |
| | THIS TIME. UABLE TO DO COMPLETE PLAN |
| | REVIEW. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | WHICH MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO TWO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |