Plan Review Notes
Plan Review Notes For Permit 04080160
Permit Number 04080160
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-19 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SEE PLANS AND APPLICATION
 CALL FOR A NEW TWO-STORY BLDG, HOWEVER
 ONLY ELECTRICAL PLANS FOR SECOND FLR
 LIGHTING AND POWER WERE SUBMITTED?
 PLEASE SEE A MIN LTS ETC FOR LS 101
 MAY BE REQUIRED.
  
 2)NOTE: PLEASE CLARIFY GENERATOR FEED?
 ATS? ETC.
 PLEASE ALSO PROVIDE NOTE FOR SIGNAGE
 PER 230.2E
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE PROVIDE ALL WIND LOAD
 INFORMATION ON EXISTING POLES TO BE
 RELOCATED OR NEW POLES.
 FBC 140 MPH
  
 **PLEASE SEE PLANS ARE NOT COMPLETE AT
 THIS TIME. UABLE TO DO COMPLETE PLAN
 REVIEW.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  