| Date |
Text |
| 2004-08-18 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)PROVIDE A COPY OF A RECORDED UNITY |
| | OF TITLE COMBINING THE TWO LOTS. |
| | OTHERWISE THE TWO LOTS MUST COMPLY WITH |
| | FBC TABLE 600 REQUIREMENTS. |
| | |
| | 2.)PROVIDE DOCUMENTATION SHOWING THE |
| | ABANDONMENT OF THE EASEMENTS, OR |
| | PROVIDE EASEMENT RELEASES. |
| | |
| | 3.)THE PRINTED NAME OF THE PERSON |
| | SEALING THE DOCUMENT IS TO BE ON |
| | EACH SHEET, FAC61G1-23.003,004. |
| | |
| | 4.)SEPARATE PERMITS REQUIRED. |
| | |
| | 5.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 6.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 7.)ENERGY CALCS REQUIRED FOR SHELL |
| | BUILDINGS, FBC13-101.1.6. |
| | |
| | 8.)THE PLANS SHOW AN OPENING BETWEEN |
| | THE FIRST FLOOR EXISTING TENANT SPACE |
| | (107) AND THE FUTURE TENANT SPACE (108). |
| | IT IS UNCLEAR HOW ENERGY (A/C) NEEDS |
| | WILL BE ADDRESSED WITH AN OPENING |
| | BETWEEN CONDITIONED AND UNCONDITIONED |
| | SPACE.IF THIS OPENING IS CLOSED, IT |
| | APPEARS THAT TWO EXITS MAY BE REQUIRED |
| | FOR THE FUTURE TENANT SPACE (108) |
| | FBC1020.1(4).PLEASE ADDRESS (LS1). |
| | |
| | 9.)LS1, FUTURE TENANT SPACE (108) |
| | SHOWS 59' TO A WINDOW.PLEASE REVISE |
| | TO SHOW EGRESS THROUGH A DOOR. |
| | |
| | 10.) INDICATE THE FIRE RESISTANCE |
| | RATING FOR THE EXIT PASSAGEWAY GOING |
| | FROM EXISTING STAIR (103) TO THE |
| | OUTSIDE.SHOW OPENING PROTECTIVES, |
| | INCLUDING WINDOWS ON THE 2ND FLOOR. |
| | PROVIDE WIDTH OF THE "NEW SIDEWALK". |
| | PROVIDE SLOPE.THE SIDEWALK IS OFFSET |
| | FROM THE DOOR; ADDRESS. |
| | |
| | 11.) EXIT PASSAGEWAYS (FBC1010.3) SHALL |
| | BE BUILT IN ACCORDANCE WITH FBC1006.1.3. |
| | 3, SHALL NOT BE USED FOR ANY PURPOSE |
| | OTHER THAN MEANS OF EGRESS.THE |
| | PASSAGEWAY FROM EXISTING STAIR (103) TO |
| | THE OUTSIDE (67 FEET) SHOWS MECHANICAL |
| | AND OTHER EQUIPMENT.ADDRESS. |
| | |
| | 12.) DOORS 08, 14 ARE TO COMPLY WITH |
| | MANEUVERING CLEARANCE, FBC11 FIGURE 25. |
| | |
| | 13.) ADDITIONAL FEES DUE (RADON). |
| | |
| | 14.) PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 15.) A6, WEST ELEVATION, PROPOSED AND |
| | EXISTING ARE MISLABELED. |
| | |
| | 16.)LS1, TABLE 600 DATA, INDICATES |
| | 14% OPENINGS FOR THE WEST WALL.THE |
| | PARAPET CANNOT BE INCLUDED AS WALL AREA. |
| | |
| | 17.)INCLUDE THE ROOFTOP MECHANICAL |
| | UNITS ON THE STRUCTURAL PLAN.PROVIDE |
| | DESIGN LOAD INFORMATION.THE |
| | ARCHITECTURALS SHOW A DIFFERENT LOCATION |
| | FOR RTU#3 THAN THE MECHANICALS. |
| | |
| | 18.)THE RELOCATED LIGHT POLE IS TO |
| | COMPLY WITH 140MPH. |
| | |
| | 19.)SIGNAGE REQUIRED PER FBC704.2.1.4 |
| | IN CORRIDOR PARTITIONS, ETC. |
| | |
| | 20.)SUBMIT TEST REPORTS FOR THE |
| | WINDOWS, STOREFRONT SYSTEM, ROOF SYSTEM, |
| | MULLIONS.FLORDIA STATE OR LOCAL |
| | PRODUCT APPROVAL REQUIRED IN ADDITION |
| | TO TEST REPORT.WWW.FLORIDABUILDING.ORG |
| | |
| | WHEN RESUBMITTING, REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED.PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED. |