| 2004-09-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHT D-1 DEMO NOTES "N" AND DEMO KEYS |
| | "11" IN THE INSTALLATION OR REMOVAL OF |
| | ANY PARY OF A DRAINAGE SYSTEM, DEAD ENDS |
| | SHALL BE PROHIBITED. |
| | 2) SHT A-1 SECTION 403.2 WHERE PLUMBING |
| | FIXTURES ARE REQUIRED, SEPARATE FACILIT- |
| | IES SHALL BE PROVIDED FOR EACH SEX. |
| | 3) SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH SECTION 11-4.15 AND ALL SUBSECTIONS |
| | FOR THE DRINKING FOUNTAIN. |
| | 4) SHT P-1 PLUMBING NOTES #13 AIR CHAMB- |
| | ERS ARE NOT APPROVED. DELETE FROM REFER- |
| | ENCE. |
| | 5)ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 - NO CERT- |
| | IFICATE OF AUTHORIZATION SHOWN. |
| | |