Plan Review Notes
Plan Review Notes For Permit 04080151
Permit Number 04080151
Review Stop P
Sequence Number 1
Notes
Date Text
2004-09-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT D-1 DEMO NOTES "N" AND DEMO KEYS
 "11" IN THE INSTALLATION OR REMOVAL OF
 ANY PARY OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED.
 2) SHT A-1 SECTION 403.2 WHERE PLUMBING
 FIXTURES ARE REQUIRED, SEPARATE FACILIT-
 IES SHALL BE PROVIDED FOR EACH SEX.
 3) SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 FOR THE DRINKING FOUNTAIN.
 4) SHT P-1 PLUMBING NOTES #13 AIR CHAMB-
 ERS ARE NOT APPROVED. DELETE FROM REFER-
 ENCE.
 5)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025 - NO CERT-
 IFICATE OF AUTHORIZATION SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]