| Plan Review Notes For Permit 04080139 |
| Permit Number |
04080139 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-02-01 00:00:00 | ********* UNSAT 3RD REVIEW******* | | | | | | PLEASE SEE NOTES 3 AND 4 FROM PREVIOUS | | | REVIEW. | | | | | | | | | 1)NOTE: NOTE #3, PLEASE SEE MISSING | | | EQUIPMENT GROUNDING CONDUCTOR FROM MAIN | | | DISC TO PANEL. | | | 250.24,250.110,250.122 | | | | | | 2)NOTE: PLEASE SEE MISSING MEANS OF DISC | | | AT DETACHED STRUCTURE PER 225.31. | | | | | | ** OWES RESUB FEE FOR THIS RESUB. | | | ** WILL ALSO OWE RESUB FOR NEXT RESUB. | | | | | | | | | PLEASE SEE ATTACHED COPY OF FS | | | 553.80(2)(B). THIS IS ONLY A NOTICE | | | GIVEN AT THIS TIME. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|