Plan Review Notes
Plan Review Notes For Permit 04080139
Permit Number 04080139
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-15 00:00:00*** UNSAT ***
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASECLARIFY IF ALUM LT POLES
 SHOWN ON PLANS ARE INCLUDED ON THIS
 PERMIT AND SCOPE OF WORK. IF THEY ARE
 INCLUDED, PLEASE INCLUDE WIND LOADING
 FOR FBC 140 MPH
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISC TO
 PANEL. 250.24,250.122
  
 4)NOTE: PLEASE NOTE: IF ELECTRICAL
 DEVICES/LOADS WILL BE ON MAIL KIOSK,
 THEN A MEANS OF DISC WILL BE REQUIRED.
 225.31 PLANS ONLY MENTIONS A J-BOX AT
 THIS TIME.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]