Plan Review Notes
Plan Review Notes For Permit 04080139
Permit Number 04080139
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-10 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE NOT ENOUGH ELECTRICAL
 INFORAMTION WAS SUBMITTED FOR REVIEW.
 PLAN ONLY INDICATES TWO LT FIXTURES ON
 WALL?
 IS THERE LIGHTING ETC AT MAILBOX/BLDG/
 SHELTER?
 PLEASE SEE 225.31 FOR MEANS OF DISC.
  
 PLEASE SHOW CIRCUIT(S), POWER FEED,
 (CONCUITS AND CONDUCTORS) AND FROM WHERE
 ?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]