| 2005-04-11 00:00:00 | DENIED: | | | SUBMITTAL DATA PLAN SHEET MSK-1 INDICATE | | | LOUVERS FOR THE REQUIRED MAKE-UP AIR. | | | THE LOUVERS APPEAR TO BE IN THE GARAGE | | | AREA.MAKE-UP AIR FOR PRODUCTS OF | | | COMBUSTION MUST COME FROM OUTDOORS AND | | | NOT FROM AN ENCLOSED PARKING GARAGE THAT | | | HAS IS OWN PRODUCTS OF COMBUSTION DUE TO | | | THE VECHICLES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|