Plan Review Notes
Plan Review Notes For Permit 04080132
Permit Number 04080132
Review Stop B
Sequence Number 1
Notes
Date Text
2004-08-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04080132
 ADD: 610 CLEMATIS ST
 CONT: SUPERIOR POOL , SPA
 TEL: (954)520-3368
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 COMMERCIAL SPA
  
 1) 412.1.ABCD.2.4.2 COVERS REQUIRED
 SPAS AND HEATED POOLS SHALL BE EQUIPPED
 WITH A COVER DESIGNED TO MINIMIZE HEAT
 LOSS.
  
 2) 412.1.ABCD.3.5 POOL & SPA HEATERS,
 ALL GAS & OIL FIRED POOL HEATERS WHEN
 TESTED IN ACCORDANCE WITH ANSI Z21.56-
 1989 SHALL HAVE A MINIMAL THERMAL
 EFFICIENCY OF 78 PERCENT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026