| Plan Review Notes For Permit 04080129 |
| Permit Number |
04080129 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-09-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424 SWIMMING POOLS | | | | | | 1) SECTION 424.1.6.5.14 THERMOSTAT REQ- | | | UIRED ON HEATER RETURN LINE. SHEET 7 | | | 2) OVERFLOW FROM COLLECTOR TANKS SHALL | | | DRAIN INTO STORM. | | | 3) FBC-2001 424.2.12.1 PRESSURE TESTS. | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (ADD TO NOTES) | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|