Plan Review Notes
Plan Review Notes For Permit 04080129
Permit Number 04080129
Review Stop P
Sequence Number 1
Notes
Date Text
2004-09-14 00:00:00DENIED
 REFERENCE: FBC-2001 424 SWIMMING POOLS
  
 1) SECTION 424.1.6.5.14 THERMOSTAT REQ-
 UIRED ON HEATER RETURN LINE. SHEET 7
 2) OVERFLOW FROM COLLECTOR TANKS SHALL
 DRAIN INTO STORM.
 3) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]