2004-08-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04080129
 ADD: 610 CLEMATIS ST
 CONT: SUPERIOR POOL & SPA
 TEL: (954)520-3368
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 COMMERCIAL POOL
  
 1) 412.1.ABCD.2.4.2 COVERS REQUIRED.
 SPAS AND HEATED POOLS SHALL BE EQUIPPED
 WITH A COVER DESIGNED TO MINIMIZE HEAT
 LOSS.
  
 2) 412.1.ABCD.3.5 POOL AND SPA HEATERS.
 ALL GAS AND OIL FIRED POOL HEATERS WHEN
 TESTED IN ACCORDANCE WITH ANSI Z21.56-
 1989 SHALL HAVE A NINIMUM THERMAL
 EFFICIENCY OF 78 PERCENT.
  
 3) PROVIDE INFORMATION ON THE CONCRETE
 FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE SIZE (CLEAR AREA) OF THE
 CONCRETE VENT IN THE POOL PUMP ROOM.
 EQUIPMENT LOCATED IN CONFINED SPACES.
  
 4)POOL PLAN SHEET 9 OF 10 "DEPTH MARKING
 DETAIL, INDICATES WHERE THE DEPTH MARKER
 SHALL BE PLACED IN THE POOL,
 424.1.2.3.1(2) THE MAXIMUM PERIMETER
 BETWEEN MARKINGS OF 25' AND SHALL BE
 LEGIBLE FROM INSIDE THE POOL AND ALSO
 FROM THE POOL DECK.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026