Plan Review Notes
Plan Review Notes For Permit 04080107
Permit Number 04080107
Review Stop P
Sequence Number 1
Notes
Date Text
2004-08-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 NFPA-99C MED-GAS
 FBC-2001 BUILDING
  
 1) SHT A.3 FINISH SCHEDULE INDICATES THE
 BASE IN THE TOILET ROOMS WILL BE WOOD.
 PLEASE INDICATE HOW THIS COMPLIES WITH
 SECTION 1204.2 WHICH STATES THE WALLS
 AND FLOORS OF ALL PUBLIC REST ROOMS
 SHALL BE LINED WITH NONABSORBENT MATER-
 IAL TO A HEIGHT OF 4' ABOVE THE FLOOR.
 2) SHT A.1 WAS IT YOUR INTENTION NOT TO
 HAVE A SINK IN PROCEDURE ROOM #2? NOTE
 NO SINK SHOWN ON FLOOR PLAN. SECTION
 104.2.1
 3) SHT A.1 SHOW CLEAR FLOOR SPACE REQUI-
 RED BY SECTION 11-4.24.5 WHICH SHALL BE
 PROVIDED IN FRONT OF THE SINKS TO ALLOW
 FORWARD APPROACH. THIS IS FOR THE SINKS
 IN THE COFFEE ROOM AND THE CONFERENCE
 ROOMS. SINKS SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT A
 DETAIL.
 4) SHTS A.1 & A.5 DETAIL 14/A5 ON SHEET
 #1 SHOWN IN TWO DIFFERENT LOCATIONS WITH
 DIFFEREN ELEVATIONS. PLEASE CLARIFY.
 SECTION 104.2.1
 5) SHT A.5 DETAIL #16 LABELED AS "OFFICE
 DESK" BUT SHOWS SINK. PLEASE CLARIFY
 SECTION 104.2.1
 6) SHT P-1 X-RAY PROCESSOR, SUBMIT MAN-
 UFACTURE SPECIFICATION/INSTALLATION
 SHEETS. THIS PROCESSOR MAY REQUIRE A
 CHEMICAL NUTRALIZER AND/OR A METAL INT-
 ERCEPTOR. IF EITHER IS REQUIRED RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE SHALL BE
 CONTACTED. WASTE ORD. #2938. TO CONTACT
 MR. COMPO (561) 837-4074.
 7) SHT P.1 UNDER COUNTER WATER HEATER
 SHALL BE ACCESSIBLE. PLEASE SUBMIT A DE-
 TAIL. SECTION 501.4.
 8) SHT P.1 INDICATE TYPE OF SINK LOCATED
 IN THE CLOSET WITH THE VACUUM AND AIR
 COMPRESSOR. SECTION 104.2.1
 9) SHT P.3 SUBMIT A VENT ISOMETRIC WITH
 PIPE SIZES TO COMFIRM COMPLIANCE WITH
 TABLE 916.1
 10) SHT P.3 ELECTRIC WATER HEATER DETAIL
 THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2. SUBMIT DETAIL
 11) SHT P.4 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 RISER DIAGRAM. SECTION 604.9 - WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9, (AT ICE MAKERS, DISH WASHERS, &
 WASH MACHINES), SHALL BE LOCATED NEAR
 THE FIXTURES, IN AN "EFFECTIVE RANGE",
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 & MANUF. INSTALL. INSTRUCTIONS.
 12) SHT WATER FILTER SHALL COMPLY WITH
 NSF-42, OR NSF-58 WHICH EVER APPLIES.
 SECTION 611.1, THRU 611.4 SUBMIT MANUF.
 SPECIFICATIONS.
 13) BACKFLOW REQUIRED AT X-RAY PROCESSOR
 PER SECTION 608.16.9
 14) SEPARATE PERMIT REQUIRED FOR THE
 MED-GAS. MED-GAS CERTIFICATION IS REQUI-
 RED FOR THE QUALIFIER, INSTALLER, AND
 THE BRAZER. THESE CERTIFICATIONS WITH
 PICTURE IDENTIFICATION IS REQUIRED AT
 THE TIME OF APPLICATION FOR PERMIT.
 15) SHT P.5 COMPRESSOR DETAIL CALLS FOR
 A 2" PVC SCHED. 30 PIPE CONNECTED TO THE
 RETURN AIR DUCT. THIS IS NOT APPROVED.
 THE AIR INTAKE SHALL BE FROM OUTSIDE THE
 BUILDING WHEN PRACTICAL OR SHALL BE LOC-
 ATED WITHIN A ROOM WHERE NO CHEMICAL-
 BASED MATERIAL IS STORED. NFPA 99C SECT-
 ION 4-5.1.1.3(E)
 16) SHT P.5 VACUUM DETAIL NOT APPROVED.
 SEE ATTACHED SHEETS (PAGE 48) FROM NFPA
 99C FIGURES 4-5.2.1.3(A) OR 4-5.2.1.3(B)
 FOR APPROVED DRAINAGE. - SEE OTHER
 SHEETS FOR DESIGN FOR VACUUM.
 17) SHT P.5 BACKFLOW REQUIRED FOR THE
 WATER SOURCE TO VACUUM PER SECTION
 608.16.9.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved