| Date |
Text |
| 2004-08-20 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | NFPA-99C MED-GAS |
| | FBC-2001 BUILDING |
| | |
| | 1) SHT A.3 FINISH SCHEDULE INDICATES THE |
| | BASE IN THE TOILET ROOMS WILL BE WOOD. |
| | PLEASE INDICATE HOW THIS COMPLIES WITH |
| | SECTION 1204.2 WHICH STATES THE WALLS |
| | AND FLOORS OF ALL PUBLIC REST ROOMS |
| | SHALL BE LINED WITH NONABSORBENT MATER- |
| | IAL TO A HEIGHT OF 4' ABOVE THE FLOOR. |
| | 2) SHT A.1 WAS IT YOUR INTENTION NOT TO |
| | HAVE A SINK IN PROCEDURE ROOM #2? NOTE |
| | NO SINK SHOWN ON FLOOR PLAN. SECTION |
| | 104.2.1 |
| | 3) SHT A.1 SHOW CLEAR FLOOR SPACE REQUI- |
| | RED BY SECTION 11-4.24.5 WHICH SHALL BE |
| | PROVIDED IN FRONT OF THE SINKS TO ALLOW |
| | FORWARD APPROACH. THIS IS FOR THE SINKS |
| | IN THE COFFEE ROOM AND THE CONFERENCE |
| | ROOMS. SINKS SHALL COMPLY WITH SECTION |
| | 11-4.24 AND ALL SUBSECTIONS. SUBMIT A |
| | DETAIL. |
| | 4) SHTS A.1 & A.5 DETAIL 14/A5 ON SHEET |
| | #1 SHOWN IN TWO DIFFERENT LOCATIONS WITH |
| | DIFFEREN ELEVATIONS. PLEASE CLARIFY. |
| | SECTION 104.2.1 |
| | 5) SHT A.5 DETAIL #16 LABELED AS "OFFICE |
| | DESK" BUT SHOWS SINK. PLEASE CLARIFY |
| | SECTION 104.2.1 |
| | 6) SHT P-1 X-RAY PROCESSOR, SUBMIT MAN- |
| | UFACTURE SPECIFICATION/INSTALLATION |
| | SHEETS. THIS PROCESSOR MAY REQUIRE A |
| | CHEMICAL NUTRALIZER AND/OR A METAL INT- |
| | ERCEPTOR. IF EITHER IS REQUIRED RODNEY |
| | COMPO, ENVIRONMENTAL COMPLIANCE SHALL BE |
| | CONTACTED. WASTE ORD. #2938. TO CONTACT |
| | MR. COMPO (561) 837-4074. |
| | 7) SHT P.1 UNDER COUNTER WATER HEATER |
| | SHALL BE ACCESSIBLE. PLEASE SUBMIT A DE- |
| | TAIL. SECTION 501.4. |
| | 8) SHT P.1 INDICATE TYPE OF SINK LOCATED |
| | IN THE CLOSET WITH THE VACUUM AND AIR |
| | COMPRESSOR. SECTION 104.2.1 |
| | 9) SHT P.3 SUBMIT A VENT ISOMETRIC WITH |
| | PIPE SIZES TO COMFIRM COMPLIANCE WITH |
| | TABLE 916.1 |
| | 10) SHT P.3 ELECTRIC WATER HEATER DETAIL |
| | THERMAL EXPANSION CONTROL IS REQUIRED |
| | PER SECTION 607.3.2. SUBMIT DETAIL |
| | 11) SHT P.4 WATER RISER DIAGRAM, AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | RISER DIAGRAM. SECTION 604.9 - WATER |
| | HAMMER ARRESTORS REQUIRED BY SECTION |
| | 604.9, (AT ICE MAKERS, DISH WASHERS, & |
| | WASH MACHINES), SHALL BE LOCATED NEAR |
| | THE FIXTURES, IN AN "EFFECTIVE RANGE", |
| | NOT IN THE CEILING AS SHOWN. PDI-WH 201 |
| | & MANUF. INSTALL. INSTRUCTIONS. |
| | 12) SHT WATER FILTER SHALL COMPLY WITH |
| | NSF-42, OR NSF-58 WHICH EVER APPLIES. |
| | SECTION 611.1, THRU 611.4 SUBMIT MANUF. |
| | SPECIFICATIONS. |
| | 13) BACKFLOW REQUIRED AT X-RAY PROCESSOR |
| | PER SECTION 608.16.9 |
| | 14) SEPARATE PERMIT REQUIRED FOR THE |
| | MED-GAS. MED-GAS CERTIFICATION IS REQUI- |
| | RED FOR THE QUALIFIER, INSTALLER, AND |
| | THE BRAZER. THESE CERTIFICATIONS WITH |
| | PICTURE IDENTIFICATION IS REQUIRED AT |
| | THE TIME OF APPLICATION FOR PERMIT. |
| | 15) SHT P.5 COMPRESSOR DETAIL CALLS FOR |
| | A 2" PVC SCHED. 30 PIPE CONNECTED TO THE |
| | RETURN AIR DUCT. THIS IS NOT APPROVED. |
| | THE AIR INTAKE SHALL BE FROM OUTSIDE THE |
| | BUILDING WHEN PRACTICAL OR SHALL BE LOC- |
| | ATED WITHIN A ROOM WHERE NO CHEMICAL- |
| | BASED MATERIAL IS STORED. NFPA 99C SECT- |
| | ION 4-5.1.1.3(E) |
| | 16) SHT P.5 VACUUM DETAIL NOT APPROVED. |
| | SEE ATTACHED SHEETS (PAGE 48) FROM NFPA |
| | 99C FIGURES 4-5.2.1.3(A) OR 4-5.2.1.3(B) |
| | FOR APPROVED DRAINAGE. - SEE OTHER |
| | SHEETS FOR DESIGN FOR VACUUM. |
| | 17) SHT P.5 BACKFLOW REQUIRED FOR THE |
| | WATER SOURCE TO VACUUM PER SECTION |
| | 608.16.9. |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |