| Plan Review Notes For Permit 04080107 |
| Permit Number |
04080107 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-27 00:00:00 | PROVISO: | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH | | | NOTIFICATION TO ALARM/STROBE IN NORMALLY | | | OCCUPPIED AREAS PER 2001 FBC(M) 606.2.1 | | | & 606.4.1. | | | | | | PLEASE PROVIDE THE MANUFACTURER | | | SUBMITTAL/INSTALLATION INSTRUCTIONS FOR | | | THE COMPRESSOR AND VACUUM WITH THE | | | THE RESUBMITTAL OF THIS PERMIT | | | APPLICATION. | | | | | | EXHAUST TERMINATIONS SHALL BE LOCATED | | | AS NOT TO RECIRCULATE BACK INTO THE | | | VENTILATION SYSTEM PER 2001 FBC(M) | | | 501.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|