 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEERS SEAL IS REQUIRED TO BE
 CHANGED TO CONTAIN THE TERM "LICENSE"
 INSTEAD OF "CERTIFICATE" PER THE BOARD
 OF ENGINEERS, AS OF 1 JANUARY, 2006. SEE
 61G15-23.001 FAC.
  
 2} PLEASE PROVIDE A SCHEDULE FOR THE
 MAIN DISCONNECT PANEL IN THE METER/MAIN
 COMBO.INCLUDE THE OCP FOR THE ATS.
  
 3} THE DISCONNECTS AT THE A/C
 COMPRESSERS AND POOL EQUIPMENT ARE IN
 VIOLATION OF 110.26. PLEASE NOTE THESE
 WERE REDLINED IN THE LAST REVIEW, AN DID
 NOT GET CHANGED ON THIS PLAN. PLEASE SEE
 THAT THE DESIGNER SEES THE REDLINED SET.
 OFTEN THEY DON'T AND THEREFORE ARE NOT
 AWARE ANY COMMENT WAS MADE.
  
 4} THE RECEPTACLES ADDED TO THE ISLAND
 ARE CONSIDERED SERVING THE COUNTERTOP
 AND THEREFORE MUST BE GFI PER
 210.8(A)(6).
  
 5} ALL KITCHEN COUNTERTOP RECEPTACLES
 MUST COMPLY WITH 210.8(A)(6}, PLEASE SEE
 REVIEWED SET.
  
 6} THE RECEPTACLE REQUIRED BY
 210.52(G)WAS REMOVED FROM THE GARAGE,
 PLEASE PUT IT BACK AND PROTECT PER
 210.8(A)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  