| Date |
Text |
| 2006-04-20 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE ENGINEERS SEAL IS REQUIRED TO BE |
| | CHANGED TO CONTAIN THE TERM "LICENSE" |
| | INSTEAD OF "CERTIFICATE" PER THE BOARD |
| | OF ENGINEERS, AS OF 1 JANUARY, 2006. SEE |
| | 61G15-23.001 FAC. |
| | |
| | 2} PLEASE PROVIDE A SCHEDULE FOR THE |
| | MAIN DISCONNECT PANEL IN THE METER/MAIN |
| | COMBO.INCLUDE THE OCP FOR THE ATS. |
| | |
| | 3} THE DISCONNECTS AT THE A/C |
| | COMPRESSERS AND POOL EQUIPMENT ARE IN |
| | VIOLATION OF 110.26. PLEASE NOTE THESE |
| | WERE REDLINED IN THE LAST REVIEW, AN DID |
| | NOT GET CHANGED ON THIS PLAN. PLEASE SEE |
| | THAT THE DESIGNER SEES THE REDLINED SET. |
| | OFTEN THEY DON'T AND THEREFORE ARE NOT |
| | AWARE ANY COMMENT WAS MADE. |
| | |
| | 4} THE RECEPTACLES ADDED TO THE ISLAND |
| | ARE CONSIDERED SERVING THE COUNTERTOP |
| | AND THEREFORE MUST BE GFI PER |
| | 210.8(A)(6). |
| | |
| | 5} ALL KITCHEN COUNTERTOP RECEPTACLES |
| | MUST COMPLY WITH 210.8(A)(6}, PLEASE SEE |
| | REVIEWED SET. |
| | |
| | 6} THE RECEPTACLE REQUIRED BY |
| | 210.52(G)WAS REMOVED FROM THE GARAGE, |
| | PLEASE PUT IT BACK AND PROTECT PER |
| | 210.8(A)(2). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |