Plan Review Notes
Plan Review Notes For Permit 04080053
Permit Number 04080053
Review Stop P
Sequence Number 1
Notes
Date Text
2004-08-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT 1 SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS.
 A) POWDER ROOM FIXTURES DO NOT REFLECT
 LAYOUT ON FLOOR PLAN. SECTION 104.2.1
 B) WASH MACHINE REQUIRES A STANDPIPE
 MIN. 2', AND A CLEANOUT 4' ABOVE THE
 FLOOR. SECTIONS 1002.1/802.4 & 708.10.
 WASH MACHINE AND LAUNDRY SINK SHALL NOT
 CONNECT TO STACK AT THE SAME ELEVATION.
 W/M SHALL CONNECT BELOW L/T. SECTION
 706.3.
 C) BATHROOM BY BEDROOM #4 THE SHOWER
 IS ON THE RIGHT SIDE OF THE W/C ON THE
 FLOOR PLAN, BUT ON THE LEFT SIDE ON THE
 RISER. THE SHOWER IS NOT VENTED AND
 SHALL CONNECT TO THE LAV BRANCH. SECTION
 104.2.1. & 901.2.1
 D) CABANA BATH SHOWER IS NOT VENTED.
 LAV SHALL CONNECT TO THE SHOWER BRANCH
 TO VENT SHOWER. SECTION 901.2.1
 E) WET BAR DOES NOT REFLECT THE FLOOR
 PLAN. WET BAR SHALL BELOCATED ON THE
 OTHER SIDE OF THE WALL FROM THE CABANA
 BATH. SECTION 104.2.1
 F) MASTER BATH DOES NOT REFLECT THE
 FLOOR PLAN, W/C ON RIGHT, TO THE LEFT
 THE BIDET, THEN THE TUB, THEN SHOWER,
 AND THE LAV IS ON THE OPPOSITE WALL.
 BIDET AND SHOWER ARE NOT VENTED AS SHOWN
 G) BATHROOM FOR BEDROOM #2, NO FITTINGS
 APPROVED FOR W/C, TUB, LAV AS SHOWN.
 W/C BETWEEN LAV AND TUB. 2" SHOWN TO W/C
 H) WASH MACHINE REQUIRES A 2' STANDPIPE
 AND A CLEANOUT 4' ABOVE THE FLOOR. SECT-
 IONS 1002.1/802.4 & 708.10
 I) NO APPROVED FITTINGS FOR CONNECTION
 OF W/C, TUB, AND LAV AS SHOWN ON RISER
 FOR BATHROOM FIXTURES FOR BATHROOM FOR
 BEDROOM #3.
 MAKE CORRECTIONS ON RISER DIAGRAM AND
 RESUBMIT FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]