| 2004-08-11 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE GROUNDING ELECTRODE CONDUCTOR |
| | SHOWN IS NOT IN COMPLIANCE WITH 250.66, |
| | MUST BE A MINIMUM #2 CU. |
| | |
| | 2} THE GROUNDING ELECTRODE SYSTEM MUST |
| | REFLECT AND NOTE, ALL AVAILABLE |
| | COMPONENTS BONDED PER 250.50. |
| | |
| | 3} THE #2 FEEDERS TO THE PANELS DO NOT |
| | COMPLY WITH 310.15(B)(6), #1 MINIMUM. |
| | |
| | 4} PLEASE INDICATE THE SIZE AND TYPE OF |
| | WIRE AND CONDUCTORS USED AS FEEDERS FOR |
| | ALL EQUIPMENT SHOWN ON THE RISER |
| | DIAGRAM. |
| | |
| | 5} SHOW THE LOCATION OF THE SERVICE |
| | EQUIPMENT ON THE PLAN. THE DICONNECT IS |
| | SHOWN ON THE RISER BUT NOT LOCATED ON |
| | PLAN. |
| | |
| | 6} THE LOAD CALCULATIONS/PANEL |
| | SCHEDULE,SHOWS ONLY ONE WATER HEATER |
| | THERE ARE |
| | TWO SHON ON THE PLAN. PLEASE ADJUST |
| | CALCULATIONS. |
| | |
| | 7} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT PER 110.9. |
| | |
| | 8} THE A/C DISCONNECT LOCATION DO NOT |
| | MEET SPACING REQUIREMENTS OF 110.26. |
| | |
| | 9} A GFI RECEPTACLE IS REQUIRED FOR |
| | SERVICE USE @ THE CONDENSING UNITS PER |
| | 210.63. |
| | |
| | 10} PANEL "A" LOCATION MAY NOT MEET 110. |
| | 26 CLEARANCE WITH PROXIMETY OF THE AIR |
| | HANDLERS. PLEASE CHECK DIMENSIONS. |
| | |
| | 11} RECEPTACLE(S) NEED TO BE ADDED OR |
| | RELOCATED TO COMPLY WITH THE SPACING |
| | REQUIREMENTS OF 210.52 IN THE DINING |
| | ROOM, LIBRARY, BEDROOM #4, BEDROOM #3, |
| | BEDROOM #2 AND THE SITTING ROOM. SEE |
| | REVIWED SET OF PLANS. |
| | |
| | 12} THE RECEPTACLE FOR THE WHIRLPOOL TUB |
| | MUST BE GFI PER 680.71 NEC. |
| | |
| | 13} SMOKE DETECTORS ARE REQUIRED TO BE |
| | LOCATED AT THE STAIRWELLS PER 905.2.2 |
| | FBC & NFPA-72 CHAPTER 8. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |