| 2004-08-17 00:00:00 | ************* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002 |
| | PLEASE INCLUDE PRINTED NAME AND LICENSE |
| | # OF PE ON TITLE BLOCK. |
| | |
| | **THIS IS ALSO REQUIRED ON ALL SHEETS |
| | AND FOR ALL TRADES/ARCH/STRUCAL/LANSCAPE |
| | PLANS. ** |
| | PLEASE 61G1-16.004 FOR ARCH/FIRM REQ'MNT |
| | |
| | 2)NOTE: PLEASE ADJUST PLANS FOR WHAT |
| | NOW SHOWS A REMOVAL OF ONE OF THE GAZEBO |
| | 'S. |
| | |
| | 3)NOTE: PLEASE SEE 225.31 FOR DISC MEANS |
| | AT DETACHED BLDGS. |
| | |
| | 4)NOTE: PLEASE SEE RISER SHOWS A GRND |
| | ROD BEING ADDED BEFORE METER?? |
| | PLEASE SEE 250.6,250.24,250.50 |
| | GRND RDS TO BE AT LOCATION OF SERVICE. |
| | |
| | PLEASE SEE SPLICING OF SEC'S AND NOTE ON |
| | PLANS FOR SPECIFIC REQUIREMENTS. |
| | |
| | 5)NOTE: PLEASE ALSO PROVIDE WIND LOAD |
| | ON PLANS. WIND LOAD CALCS WERE SUBMITTED |
| | AND WILL STILL BE REVIEWED BY BLDG PLAN |
| | REVIEW. PLANS DO NOT SEEM TO CORRELATE |
| | FOR STRUCTUAL DETAIL. |
| | |
| | 6)NOTE: PLEASE PROVIDE INFORMATION ON |
| | MEANS OF DISCONNECT FOR SERVICE EQUIP- |
| | -MENT. 230.76,230.79, 110.27. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |