| Plan Review Notes For Permit 04071424 |
| Permit Number |
04071424 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-04 00:00:00 | | | | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | THE GEC MUST BE #2 PER 250.66. SEE RISER | | | | | | A #6 GROUND MUST BE INSTALLED IN THE | | | CONDUIT FROM THE DISCONNECT TO THE | | | PANELS. 250.122. | | | | | | THESE REDLINED PROVISO ITEMS MUST BE | | | CORRECTED ON THE PLANS OR REVISIONS NEXT | | | SUBMITTED. IF NOT CORRECTED THE | | | REVISION WILL BE FAILED. PLEASE SEE | | | THAT THE ARCHITECT READS THIS PROVISO. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|