| 2004-08-05 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04071423 |
| | ADD: 625 N FLAGLER DR# 700 |
| | CONT: SGRA. LOURDES GURREA |
| | TEL: (954) 961-6806 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | PLANS DO NOT INDICATE WHAT THE RATING |
| | IS ON THE FRONT ENTRY DOORS WILL BE, IT |
| | IS IN A HIGHLIGHTED AREA WORK TO BE |
| | COMPLETED? |
| | |
| | 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 4) SHEET A-101 SEE NEW OFFICE 0712A, |
| | IN FRONT OF THIS NEW OFFICE THERE IS A |
| | EXISTING COLUMN. WITH THE CREATION OF |
| | THE NEW OFFICE IT APPEARS TO BE LESS |
| | THAN 30" CLEAR.MEANS OF EGRESS REQUIRES |
| | 44", 36" FOR CORRIDORS WITH AN OCCUPANT |
| | LOAD LESS THAN 50. |
| | |
| | 5) PROVIDE THE MINIMUM BUILDING TYPE? |
| | 7 STORIES SHOULD REQUIRE TYPE II , |
| | 609.2.1 PARTITIONS AND BACKING ARE TO BE |
| | NONCOMBUSTIBLE. |
| | |
| | 8)11-4.1.6(2) DUTY TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| | AREAS SHALL BE DEEMED DISPROPORTIONATE |
| | TO THE OVERALL ALTERATION WHEN THE COST |
| | EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| | TION TO THE PRIMARY FUNCTION AREA. |
| | (A)(I) AN ACCESSIBLE ENTRANCE |
| | (II) AN ACCESSIBLE ROUTE |
| | (III) AT LEAST ONE ACCESSIBLE REST- |
| | ROOM FOR EACH SEX OR A SINGLE |
| | UNISEX RESTROOM |
| | (IIII) ACCESSIBLE TELEPHONE |
| | (IV) ELEMENTS SUCH AS PARKING, STOR- |
| | AGE OR ALARMS. |
| | OFFICE 708, THE ENTRY DOES NOT MEET THE |
| | REQUIRED 18" CLEAR ON THE PULL SIDE OF |
| | THE OFFICE DOORWAY. |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 9)DOES THIS BUILDING HAVE FIRE SPRINKLER |
| | SYSTEM? IF SO PROVIDE UPDATES TO THIS |
| | FLOOR. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |