| Notes |
| Date |
Text |
| 2004-08-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SANITARY RISER DIAGRAM DO NOT MEET | | | CODE REQUIREMENTS. | | | A) GUEST HOUSE, WASH MACHINE SHALL DIS- | | | CHARGE DOWNSTREAM OF THE WET VENT FOR | | | THE BATHROOM. SECTION 909.1 - KITCHEN | | | SINK ALSO SHALL DISCHARGE DOWNSTREAM OF | | | WET VENT. | | | B) NOT AN APPROVED FITTING AS SHOWN FOR | | | FIXTURES. | | | C) WASH MACHINE REQUIRES A STANDPIPE & | | | A CLEANOUT 4' ABOVE THE FLOOR. SECTIONS | | | 1002.1/802.4 & 708.10 | | | (SEE EXAMPLE OF RISER DIAGRAM THAT MEETS | | | CODE REQUIREMENTS FOR GUEST HOUSE. USE | | | THIS EXAMPLE TO MAKE THE FOLLOWING CORR- | | | ECTIONS). MAIN HOUSE RISER DOES NOT MEET | | | CODE REQUIREMENTS. | | | A) WASH MACHINE REQUIRES A STANDPIPE & | | | A CLEANOUT 4' ABOVE THE FLOOR. SECTIONS | | | 1002.1/802.4 & 708.10. | | | B) NOT AN APPROVED FITTING PICKING UP | | | BATHROOM FIXTURES. (SEE ABOVE REFERENCED | | | EXAMPLE). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|