2004-08-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DO NOT MEET
 CODE REQUIREMENTS.
 A) GUEST HOUSE, WASH MACHINE SHALL DIS-
 CHARGE DOWNSTREAM OF THE WET VENT FOR
 THE BATHROOM. SECTION 909.1 - KITCHEN
 SINK ALSO SHALL DISCHARGE DOWNSTREAM OF
 WET VENT.
 B) NOT AN APPROVED FITTING AS SHOWN FOR
 FIXTURES.
 C) WASH MACHINE REQUIRES A STANDPIPE &
 A CLEANOUT 4' ABOVE THE FLOOR. SECTIONS
 1002.1/802.4 & 708.10
 (SEE EXAMPLE OF RISER DIAGRAM THAT MEETS
 CODE REQUIREMENTS FOR GUEST HOUSE. USE
 THIS EXAMPLE TO MAKE THE FOLLOWING CORR-
 ECTIONS). MAIN HOUSE RISER DOES NOT MEET
 CODE REQUIREMENTS.
 A) WASH MACHINE REQUIRES A STANDPIPE &
 A CLEANOUT 4' ABOVE THE FLOOR. SECTIONS
 1002.1/802.4 & 708.10.
 B) NOT AN APPROVED FITTING PICKING UP
 BATHROOM FIXTURES. (SEE ABOVE REFERENCED
 EXAMPLE).
  