Plan Review Notes
Plan Review Notes For Permit 04071384
Permit Number 04071384
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-10 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE #3 CONDUCTORS FEEDING THE 200
 AMP PANEL FROM THE DISCONNECT ON THE
 RISER
 DIAGRAM ARE TOO SMALL. THEY MUST BE 2/0
 OR LARGER, SEE 210.15(B)(6), 2002 NEC.
  
 2} THE DISCONNECT LOCATED AT THE MAIN
 HOUSE (SEPERATE STRUCTURE) MUST BE
 GROUNDED PER 250.32. SHOW SAME ON PLAN.
  
 3} PANELBOARD "A" SHOWS THE BATHROOMS ON
 "AFI". PLEASE NOTE THIS IS NOT
 REQUIRED, ONLY GFI AND ARTICLE
 210.11(C)(3), SEPERATE CIRCUIT, ARE
 REQUIRED.
  
 THE FOLLOWING COMMENTS ARE FOR THE MAIN
 HOUSE.
  
 4} PLEASE SEE MISSING RECEPTACLES,
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 5} A SMOKE DETECTOR IS REQUIRED AT THE
 STAIRWELL PER 905.2.2 2001 FBC.
  
 6} BEDROOM #2 NEEDS AN ADDED RECEPTACLE
 PER 210.52(A)(1), SEE REVIEWED PLAN.
  
 7} PLEASE SEE 8-1.4.2 NFPA-72 FOR
 DISTANCE FROM BATH REQUIREMENT RE:
 SMOKE DETECTORS.
  
 8} THE DISCONNECT LOCATION AT A/C DOES
 NOT MEET THE CLEARANCE REQUIREMENTS OF
 110.26.
  
 9} THE PANEL LOCATION WITH RESPECT TO
 THE KITCHEN COUNTER DOES NOT GIVE 36"
 CLEARANCE REQUIRED PER 110.26.
  
 THESE NOTES ARE SPECIFIC TO THE GUEST
 HOUSE.
  
 10} LIST THE BATH CIRCUIT PER
 210.11(C)(3) ON THE SCHEDULE, #12@20AMP.
  
 11} THE DISCONNECT FOR THE CONDENSING
 UNIT DOES NOT MEET 110.26 REQUIREMENTS.
  
 12} PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF THE UNIT PER
 210.52(E).
  
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026