Plan Review Notes
Plan Review Notes For Permit 04071332
Permit Number 04071332
Review Stop M
Sequence Number 3
Notes
Date Text
2005-02-25 00:00:00NO MECHANICAL CONTRACTOR INDICATED ON
 THE PERMIT APPLICATION.PER ARCHITECT'S
 NOTE, A/C CONTRACTOR TO SUBMIT PLANS FOR
 HIS APPROVAL.SEPARATE PERMIT REQUIRED
 FOR MECHANICAL, PLEASE PROVIDE PLANS AND
 MANUAL J CALCULATIONS WITH PERMIT
 APPLICATION.ENERGY CALCS SUBMITTED
 WITH THE BUILDING PERMIT APPLICATION.
 1.PLAN SHEET A.4, MECHANICAL FLOOR
 PLAN NOTES; A/C CONTRACTOR TO PROVIDE
 SHOP DRAWINGS FOR ARCHITECT'S APPROVAL.
 PLEASE REVISE THE PLANS TO INDICATE THE
 FOLLOWING -
 - RETURN AIR REQUIRED FROM HABITABLE
 ROOMS ISOLATED FROM THE RETURN AIR BACK
 TO THE AIR HANDLING UNIT 2001
 FBC(M)601.4.
 - INDICATE LINE SIZES FOR THE LIQUID,
 SUCTION & CONDENSATE.PLEASE NOTE,
 CONDENSATE TO TERMINATE A MINIMUM OF 12"
 FROM THE BUILDING STRUCTURE.
 - PROVIDE DUCT AND GRILLE SIZE.
 - AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001
 FBC(M)307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.