| Plan Review Notes For Permit 04071332 |
| Permit Number |
04071332 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-02-25 00:00:00 | NO MECHANICAL CONTRACTOR INDICATED ON | | | THE PERMIT APPLICATION.PER ARCHITECT'S | | | NOTE, A/C CONTRACTOR TO SUBMIT PLANS FOR | | | HIS APPROVAL.SEPARATE PERMIT REQUIRED | | | FOR MECHANICAL, PLEASE PROVIDE PLANS AND | | | MANUAL J CALCULATIONS WITH PERMIT | | | APPLICATION.ENERGY CALCS SUBMITTED | | | WITH THE BUILDING PERMIT APPLICATION. | | | 1.PLAN SHEET A.4, MECHANICAL FLOOR | | | PLAN NOTES; A/C CONTRACTOR TO PROVIDE | | | SHOP DRAWINGS FOR ARCHITECT'S APPROVAL. | | | PLEASE REVISE THE PLANS TO INDICATE THE | | | FOLLOWING - | | | - RETURN AIR REQUIRED FROM HABITABLE | | | ROOMS ISOLATED FROM THE RETURN AIR BACK | | | TO THE AIR HANDLING UNIT 2001 | | | FBC(M)601.4. | | | - INDICATE LINE SIZES FOR THE LIQUID, | | | SUCTION & CONDENSATE.PLEASE NOTE, | | | CONDENSATE TO TERMINATE A MINIMUM OF 12" | | | FROM THE BUILDING STRUCTURE. | | | - PROVIDE DUCT AND GRILLE SIZE. | | | - AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 | | | FBC(M)307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|