| Plan Review Notes For Permit 04071332 |
| Permit Number |
04071332 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-01-03 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR ALL NEW | | | SERVICE EQUIPMENT BEING INSTALL- ED. | | | MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9. | | | | | | 2} INDICATE GROUNDING ELECTRODE SYSTEM | | | PER 250.50 & 250.66, INCLUDE ON PLAN. | | | | | | 3} BEDROOM #2 NEEDS A RECEPTACLE ADDED | | | TO COMPLY WITH 210.52(A)(1). | | | | | | 4} THE ARCHITECTS SEAL PER 61G1-16.001, | | | MUST BE ON PLAN. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|