| 2005-01-13 00:00:00 | DENIED |
| | |
| | |
| | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| | RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | 2.SUBMIT TWO COMPLETE SETS OF PRODUCT |
| | APPROVALS FOR THE FOLLOWING, GLASS |
| | BLOCK, STRAPS AND TIE-DOWNS, WINDOWS, |
| | EXTERIOR DOORS, IMPACT PROTECTION FOR |
| | EXT. DOORS, AND ROOFING. |
| | ALL PRODUCT APPROVALS REQUIRE THE |
| | FOLLOWING TO BE ATTACHED TO EACH |
| | APPROVAL. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | NEW NOTES: |
| | |
| | A. PLANS SHOW ALL EXTERIOR DOORS AS |
| | EXISTING, BUT PRODUCT APPROVALS HAVE |
| | BEEN SUBMITTED FOR EXTERIOR DOORS. |
| | PLEASE VERIFY ON PLANS. |
| | |
| | B.BUILDING VALUATION IS TOO LOW. |
| | ADJUST VALUATION TO REFLECT WORK ON NEW |
| | PLANS SUBMITTED.ADDITIONAL PERMIT FEES |
| | ARE DUE. |
| | |
| | C.SHOW SIZE AND LOCATION OF ATTIC |
| | ACCESS. FBC 2309.6 |
| | |
| | D. WATER STOP - WHERE EXTERIOR MASONARY |
| | UNITS BEAR ON A CONCRETE FLOOR SURFACE, |
| | A 1.5" RECESS SHALL BE PROVIDED TO |
| | MINIMIZE WATER INTRUSION. WPB |
| | AMMENDMENTS TO THE FBC 2111.1.9 |
| | |
| | E.ON 2 X 8 PT TOP PLATE, SHOW SIZE AND |
| | TYPE OF ANCHOR AND SPACING. |
| | |
| | F. PLEASE SUBMIT 2 COPIES OF MANUAL J |
| | ENERGY CALCS. |
| | |
| | G.THE ARCHITECTS SEAL IS REQUIRED PER |
| | 61G1-16.001 PLEASE PUT SEAL ON ALL |
| | PAGES |
| | AND SIGN. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |